Transformers – Twiclo Electrical Industries https://www.twicloelectrical.com My WordPress Blog Tue, 03 Jun 2025 16:27:47 +0000 en-US hourly 1 https://wordpress.org/?v=6.9.4 244895093 33 kV CURRENT TRANSFORMERS FOR HIGHER CURRENT RATIO https://www.twicloelectrical.com/portfolio/33-kv-current-transformers-for-higher-current-ratio/ Tue, 14 Jun 2022 16:19:48 +0000 http://www.twicloelectrical.com/?post_type=portfolio&p=278 33 kV CURRENT TRANSFORMERS FOR HIGHER CURRENT RATIO
1. Name and address of Manufacturer :  Twiclo Electrical Industries, Raipur
2. Type :  Outdoor, Oil filled, Vacuum Impregnated
3. Manufacturer’s Designation :  COF
4. Rated Voltage/Highest Voltage :  33 kV / 36 kV *
5. Rated Primary Current :  As per spec Amps *
6.  Secondary Core details :
     a. Number of Cores :  One
     b. Rated Secondary Current :  1 or 5 Amp *
     c. Rated Output :  as per spec VA *
     d. Class of accuracy :  as per spec VA *
     e. Accuracy limit factor :  as per spec VA *
7.  Turns Ratio :   Nominally same as transformation ratio
8.  Short time thermal current & its duration :  As per spec kA
9.  Rated dynamic current (peak value) :  2.5 times of short time thermal current kA*
10.     a. Rated continuous thermal current :  Same as rated primary current *
           b. Temperature rise over ambient :  Within limits prescribed by IS. *
11.  Impulse withstand test voltage :  170 kV (Peak)*
12.  One-minute power frequency dry/wet withstand test voltage on primary :  70 kV *
13.  One-minute power frequency withstand test voltage on secondary :  3 kV *
14.  Total creepage of insulator :  900 mm minimum *
15.  Whether CT is hermetically sealed :  Yes.
16.  Quantity of oil :  Approx. 16 Liters.
17.  Total weight :  Approx. 70 Kgs
18.  Mounting Details :  As per drawing
19.  Equipment conforms to specification :  IS 2705
20.  Overall dimensions :  As per our drawing

Note: Only items marked * are guaranteed. All others are indicative and subject to change.

]]>
278
33 kV CURRENT TRANSFORMERS DUAL RATIO https://www.twicloelectrical.com/portfolio/33-kv-current-transformers-dual-ratio/ Tue, 14 Jun 2022 16:18:23 +0000 http://www.twicloelectrical.com/?post_type=portfolio&p=276 33 kV CURRENT TRANSFORMERS DUAL RATIO
1. Name and address of Manufacturer : Twiclo Electrical Industries, Raipur
2. Type :  Outdoor, Oil filled, Vacuum Impregnated
3. Manufacturer’s Designation :  COD
4. Rated Voltage/Highest Voltage :  33 kV / 36 kV *
5. Rated Primary Current :  As per spec Amps *
6.  Secondary Core details
     a. Number of Cores :  Two
 Core 1  Core 2
     b. Rated Secondary Current :  1 or 5 Amp *  1 or 5 Amp *
     c. Rated Output :  as per spec VA *  as per spec VA *
     d. Class of accuracy :  as per spec VA * as per spec VA *
     e. Accuracy limit factor :  as per spec VA * as per spec VA *
7.  Turns Ratio :   Nominally same as transformation ratio
8.  Short time thermal current & its duration :  As per spec kA
9.  Rated dynamic current (peak value) :  2.5 times of short time thermal current kA*
10.     a. Rated continuous thermal current :  Same as rated primary current *
           b. Temperature rise over ambient :  Within limits prescribed by IS. *
11.  Impulse withstand test voltage :  170 kV(Peak)*
12.  One-minute power frequency dry/wet withstand test voltage on primary :  70 kV *
13.  One-minute power frequency withstand test voltage on secondary :  3 kV *
14.  Total creepage of insulator :  900 mm minimum *
15.  Whether CT is hermetically sealed :  Yes.
16.  Quantity of oil :  Approx. 16 Liters.
17.  Total weight :  Approx. 70 Kgs
18.  Mounting Details :  As per drawing
19.  Equipment conforms to specification :  IS 2705
20.  Overall dimensions :  As per our drawing

Note: Only items marked * are guaranteed. All others are indicative and subject to change.

]]>
276
33kV SINGLEPHASE POTENTIAL TRANSFORMERS https://www.twicloelectrical.com/portfolio/33kv-singlephase-potential-transformers/ Tue, 14 Jun 2022 16:17:05 +0000 http://www.twicloelectrical.com/?post_type=portfolio&p=274 33kV SINGLEPHASE POTENTIAL TRANSFORMERS
1. Name and address of Manufacturer : Twiclo Electrical Industries, Raipur
2. Manufacturer’s type & Designation :  Oil Filled, Vacuum Impregnated: VOD
3. Nature of service :  Outdoor *
4. Type of Cooling :  ON *
5.  System characteristics :
     a. Rated system voltage :  33kV
     b. Highest system voltage :  36 kV
     c. Rated system frequency :  50 Hz
     d. Nature of neutral earthing :  Effective
6.  Rated voltage ratio :   (33000/√3) / (110/√3)*
7.  Winding Connections :  NA as single phase
8.  Rated Burden :  As per spec VA *
9.  Class of Accuracy :  As per spec *
10.  Polarity :  Not applicable
11.  Rated voltage factor and time :  1.2 continuous; 1.5 / 30 sec *
12.  Limits of ratio and phase error :  Within limits specified by IS
13.  Temperature rise of top oil at 1.2 times rated primary voltage with rated secondary :  Within limits specified by IS
14.  Secondary Core details :
     a. Type :  Outdoor, Glazed Porcelain to IS 5621. *
     b. Electrical characteristics :  To IS 5621 *
     c. Total creepage distance :  900 mm minimum. *
15.  One-minute power frequency withstand test on primary winding :  70 kV induced; 3 kV applied. *
16.  One-minute power frequency withstand test on secondary winding :  3 kV. *
17.  High voltage impulse withstand test on primary windings :  170 kV. *
18.  Oil
     a. Specification :  To IS 335 *
     b. Quantity for First Filling :  Approx. 30 Litres.
19.  Total weight of P.T. with oil :  Approx. 90 Kgs.
20.  Equipment conforms to specification :  IS 3156
21.  Outline dimensional drawing with mounting details :  As per our drawing

Note: Only items marked * are guaranteed. All others are indicative and subject to change.

]]>
274
11 kV INDOOR METERING SET https://www.twicloelectrical.com/portfolio/11-kv-indoor-metering-set/ Tue, 14 Jun 2022 16:12:05 +0000 http://www.twicloelectrical.com/?post_type=portfolio&p=272 11 kV INDOOR METERING SET
1. Name and address of Manufacturer : Twiclo Electrical Industries, Raipur
2. Type :  Outdoor, Oil filled, Vacuum Impregnated : MOD/CB
3.  Nature of service :  Outdoor *
4.  Type of Cooling :  ON *
5.  System characteristics :
     a. Rated system voltage :  11 kV
     b. Highest system voltage :  12 kV
     c. Rated system frequency :  50 Hz
6.  Oil
     a. Specification :  To IS 335 *
     b. Quantity for First Filling :  Approx. 60 liters.
7.  Total weight with oil :   Approx. 200 Kgs.
8.  Outline dimensional drawing with mounting details :  As per drawing
9.  Mounting Details :  As per drawing
10.  Overall dimensions :  As per drawing
a.) Voltage Transformer
1.  Rated voltage ratio :  (11000) / (110) *
2.  Winding Connections :  Star-Star
3.  Rated Burden :  10 VA *
4.  Class of Accuracy :  0.2*
5.  Rated voltage factor and time :  1.2 continuous *
6.  Limits of ratio and phase error :  Within limits specified by IS
7.  Temperature rise of top oil at 1.2 times rated primary voltage with rated secondary :  Within limits specified by IS
8.  H.V. Bushing Characteristics
     a. Type :  Outdoor/ Indoor, Glazed Porcelain *
     b. Make :  Suitable indigenous
     c. Electrical characteristics :  To IS 2099 / 1996 *
9.  One-minute power frequency withstand test on primary winding kV rms :  28 *
10.  One-minute power frequency withstand test on secondary winding kV rms :  3 *
11.  High voltage impulse withstand test on primary windings kV peak :  75 *
12.  Reference specification to which the equipment conform :  IS 3156 / 1992
b.) Current Transformer
1.  Rated Voltage/Highest Voltage :  11 kV / 12 kV *
2.  Rated Primary Current :  Amps *
3.  Secondary Core details
     a. Rated Secondary Current :  5 Amp *
     b. Rated Output :  Rated Output
     c. Class of accuracy :  0.2S *
     d. Accuracy limit factor :  NA *
4.  Turns Ratio :  Nominally same as transformation ratio
5.  Short time thermal current & its duration :  To suit system fault level
6.  Rated dynamic current (peak value) :  2.5 * Short Time Current Rating
7.     a. Rated continuous thermal current :  120% of rated primary current *
        b. Temperature rise over ambient :  Within limits prescribed by IS. *
8.  Impulse withstand test voltage kV Peak :  75 *
9.  One-minute power frequency dry/wet withstand test voltage on primary kV rms :  28 *
10.  One-minute power frequency withstand test voltage on secondary kV rms :  3 *
11.  Reference specification to which the equipment conform :  IS 2705 / 1992

Note: Only items marked * are guaranteed. All others are indicative and subject to change.

]]>
272
11 kV SEMI-INDOOR METERING SET https://www.twicloelectrical.com/portfolio/11-kv-semi-indoor-metering-set/ Tue, 14 Jun 2022 16:10:21 +0000 http://www.twicloelectrical.com/?post_type=portfolio&p=270 11 kV SEMI-INDOOR METERING SET
1. Name and address of Manufacturer : Twiclo Electrical Industries, Raipur
2. Type :  Outdoor, Oil filled, Vacuum Impregnated : MOD/CB
3.  Nature of service :  Outdoor *
4.  Type of Cooling :  ON *
5.  System characteristics :
     a. Rated system voltage :  11 kV
     b. Highest system voltage :  12 kV
     c. Rated system frequency :  50 Hz
6.  Oil
     a. Specification :  To IS 335 *
     b. Quantity for First Filling :  Approx. 60 liters.
7.  Total weight with oil :   Approx. 200 Kgs.
8.  Outline dimensional drawing with mounting details :  As per drawing
9.  Mounting Details :  As per drawing
10.  Overall dimensions :  As per drawing
a.) Voltage Transformer
1.  Rated voltage ratio :  (11000) / (110) *
2.  Winding Connections :  Star-Star
3.  Rated Burden :  10 VA *
4.  Class of Accuracy :  0.2*
5.  Rated voltage factor and time :  1.2 continuous *
6.  Limits of ratio and phase error :  Within limits specified by IS
7.  Temperature rise of top oil at 1.2 times rated primary voltage with rated secondary :  Within limits specified by IS
8.  H.V. Bushing Characteristics
     a. Type :  Outdoor/ Indoor, Glazed Porcelain *
     b. Make :  Suitable indigenous
     c. Electrical characteristics :  To IS 2099 / 1996 *
9.  One-minute power frequency withstand test on primary winding kV rms :  28 *
10.  One-minute power frequency withstand test on secondary winding kV rms :  3 *
11.  High voltage impulse withstand test on primary windings kV peak :  75 *
12.  Reference specification to which the equipment conform :  IS 3156 / 1992
b.) Current Transformer
1.  Rated Voltage/Highest Voltage :  11 kV / 12 kV *
2.  Rated Primary Current :  Amps *
3.  Secondary Core details
     a. Rated Secondary Current :  5 Amp *
     b. Rated Output :  Rated Output
     c. Class of accuracy :  0.2S *
     d. Accuracy limit factor :  NA *
4.  Turns Ratio :  Nominally same as transformation ratio
5.  Short time thermal current & its duration :  To suit system fault level
6.  Rated dynamic current (peak value) :  2.5 * Short Time Current Rating
7.     a. Rated continuous thermal current :  120% of rated primary current *
        b. Temperature rise over ambient :  Within limits prescribed by IS. *
8.  Impulse withstand test voltage kV Peak :  75 *
9.  One-minute power frequency dry/wet withstand test voltage on primary kV rms :  28 *
10.  One-minute power frequency withstand test voltage on secondary kV rms :  3 *
11.  Reference specification to which the equipment conform :  IS 2705 / 1992

Note: Only items marked * are guaranteed. All others are indicative and subject to change.

]]>
270
33kV Current Transformer https://www.twicloelectrical.com/portfolio/33kv-current-transformer/ Mon, 13 Jun 2022 17:28:27 +0000 http://www.twicloelectrical.com/?post_type=portfolio&p=268 33kV CURRENT TRANSFORMERS
1. Name and address of Manufacturer : Twiclo Electrical Industries, Raipur
2. Type :  Outdoor, Oil filled, Vacuum Impregnated
3. Manufacturer’s Designation :  COD
4. Rated Voltage/Highest Voltage :  33 kV / 36 kV *
5. Rated Primary Current :  As per spec Amps *
6.  Secondary Core details :
     a. Number of Cores :  One
     b. Rated Secondary Current :  1 or 5 Amp *
     c. Rated Output :  as per spec VA *
     d. Class of accuracy :  as per spec VA *
     e. Accuracy limit factor :  as per spec VA *
7.  Turns Ratio :   Nominally same as transformation ratio
8.  Short time thermal current & its duration :  As per spec kA
9.  Rated dynamic current (peak value) :  2.5 times of short time thermal current kA*
10.     a. Rated continuous thermal current :  Same as rated primary current *
           b. Temperature rise over ambient :  Within limits prescribed by IS. *
11.  Impulse withstand test voltage :  170 kV (Peak)*
12.  One-minute power frequency dry/wet withstand test voltage on primary :  70 kV *
13.  One-minute power frequency withstand test voltage on secondary :  3 kV *
14.  Total creepage of insulator :  900 mm minimum *
15.  Whether CT is hermetically sealed :  Yes.
16.  Quantity of oil :  Approx. 16 Liters.
17.  Total weight :  Approx. 70 Kgs
18.  Mounting Details :  As per drawing
19.  Equipment conforms to specification :  IS 2705
20.  Overall dimensions :  As per our drawing

Note: Only items marked * are guaranteed. All others are indicative and subject to change.

]]>
268
11kV Current Transformer Dual Ratio https://www.twicloelectrical.com/portfolio/11kv-current-transformer-dual-ratio/ Mon, 13 Jun 2022 17:26:44 +0000 http://www.twicloelectrical.com/?post_type=portfolio&p=266 11 kV CURRENT TRANSFORMERS DUAL RATIO
1. Name and address of Manufacturer : Twiclo Electrical Industries, Raipur
2. Type :  Outdoor, Oil filled, Vacuum Impregnated
3. Manufacturer’s Designation :  COD
4. Rated Voltage/Highest Voltage :  11 kV / 12 kV *
5. Rated Primary Current :  As per spec Amps *
6.  Secondary Core details
     a. Number of Cores :  Two
 Core 1  Core 2
     b. Rated Secondary Current :  1 or 5 Amp *  1 or 5 Amp *
     c. Rated Output :  as per spec VA *  as per spec VA *
     d. Class of accuracy :  as per spec VA * as per spec VA *
     e. Accuracy limit factor :  as per spec VA * as per spec VA *
7.  Turns Ratio :   Nominally same as transformation ratio
8.  Short time thermal current & its duration :  As per spec kA
9.  Rated dynamic current (peak value) :  2.5 times of short time thermal current kA*
10.     a. Rated continuous thermal current :  Same as rated primary current *
           b. Temperature rise over ambient :  Within limits prescribed by IS. *
11.  Impulse withstand test voltage :  75 kV(Peak)*
12.  One-minute power frequency dry/wet withstand test voltage on primary :  28 kV *
13.  One-minute power frequency withstand test voltage on secondary :  3 kV *
14.  Total creepage of insulator :  300 mm minimum *
15.  Whether CT is hermetically sealed :  Yes.
16.  Quantity of oil :  Approx. 12 Liters.
17.  Total weight :  Approx. 50 Kgs
18.  Mounting Details :  As per drawing
19.  Equipment conforms to specification :  IS 2705
20.  Overall dimensions :  As per our drawing

Note: Only items marked * are guaranteed. All others are indicative and subject to change.

]]>
266
11kV Single Phase Potential Transformer https://www.twicloelectrical.com/portfolio/11kv-single-phase-potential-transformer/ Mon, 13 Jun 2022 17:24:25 +0000 http://www.twicloelectrical.com/?post_type=portfolio&p=264 11kV Single Phase Potential Transformer
1. Name and address of Manufacturer : Twiclo Electrical Industries, Raipur
2. Manufacturer’s type & Designation :  Oil Filled, Vacuum Impregnated: VOD
3. Nature of service :  Outdoor *
4. Type of Cooling :  ON *
5.  System characteristics :
     a. Rated system voltage :  11kV
     b. Highest system voltage :  12 kV
     c. Rated system frequency :  50 Hz
     d. Nature of neutral earthing :  Effective
6.  Rated voltage ratio :   (11000/√3) / (110/√3)*
7.  Winding Connections :  NA as single phase
8.  Rated Burden :  As per spec VA *
9.  Class of Accuracy :  As per spec *
10.  Polarity :  Not applicable
11.  Rated voltage factor and time :  1.2 continuous; 1.5 / 30 sec *
12.  Limits of ratio and phase error :  Within limits specified by IS
13.  Temperature rise of top oil at 1.2 times rated primary voltage with rated secondary :  Within limits specified by IS
14.  Secondary Core details :
     a. Type :  Outdoor, Glazed Porcelain to IS 5621. *
     b. Electrical characteristics :  To IS 5621 *
     c. Total creepage distance :  300 mm minimum. *
15.  One-minute power frequency withstand test on primary winding :  28 kV induced; 3 kV applied. *
16.  One-minute power frequency withstand test on secondary winding :  3 kV. *
17.  High voltage impulse withstand test on primary windings :  75 kV. *
18.  Oil :
     a. Specification :  To IS 335 *
     b. Quantity for First Filling :  Approx. 15 Litres.
19.  Equipment conforms to specification :  IS 3156
20.  Outline dimensional drawing with mounting details :  As per our drawing

Note: Only items marked * are guaranteed. All others are indicative and subject to change.

]]>
264
11kV CURRENT TRANSFORMERS https://www.twicloelectrical.com/portfolio/11kv-current-transformers/ Mon, 13 Jun 2022 17:22:02 +0000 http://www.twicloelectrical.com/?post_type=portfolio&p=262 11kV CURRENT TRANSFORMERS
1. Name and address of Manufacturer : Twiclo Electrical Industries, Raipur
2. Type :  Outdoor, Oil filled, Vacuum Impregnated
3. Manufacturer’s Designation :  COD
4. Rated Voltage/Highest Voltage :  11 kV / 12 kV *
5. Rated Primary Current :  As per spec Amps *
6.  Secondary Core details :
     a. Number of Cores :  One
     b. Rated Secondary Current :  1 or 5 Amp *
     c. Rated Output :  as per spec VA *
     d. Class of accuracy :  as per spec VA *
     e. Accuracy limit factor :  as per spec VA *
7.  Turns Ratio :   Nominally same as transformation ratio
8.  Short time thermal current & its duration :  As per spec kA
9.  Rated dynamic current (peak value) :  2.5 times of short time thermal current kA*
10.     a. Rated continuous thermal current :  Same as rated primary current *
           b. Temperature rise over ambient :  Within limits prescribed by IS. *
11.  Impulse withstand test voltage :  75 kV(Peak)*
12.  One-minute power frequency dry/wet withstand test voltage on primary :  28 kV *
13.  One-minute power frequency withstand test voltage on secondary :  3 kV *
14.  Total creepage of insulator :  300 mm minimum *
15.  Whether CT is hermetically sealed :  Yes.
16.  Quantity of oil :  Approx. 12 Liters.
17.  Total weight :  Approx. 50 Kgs
18.  Mounting Details :  As per drawing
19.  Equipment conforms to specification :  IS 2705
20.  Overall dimensions :  As per our drawing

Note: Only items marked * are guaranteed. All others are indicative and subject to change.

]]>
262
11kV 3 Phase Potential Transformer https://www.twicloelectrical.com/portfolio/11kv-3-phase-potential-transformer/ Mon, 13 Jun 2022 17:19:55 +0000 http://www.twicloelectrical.com/?post_type=portfolio&p=260 11kV 3PHASE POTENTIAL TRANSFORMERS
1. Name and address of Manufacturer : Twiclo Electrical Industries, Raipur
2. Manufacturer’s type & Designation :  Outdoor, Oil filled, Vacuum Impregnated;VOD
3. Nature of service :  Outdoor *
4. Type of Cooling :  ON *
5.  System characteristics :
     a. Rated system voltage :  11 kV
     b. Highest system voltage :  12 kV
     c. Rated system frequency :  50 Hz
     d. Nature of neutral earthing :  Effective
6.  Rated voltage ratio :   11000 / 110 *
7.  No of Phases :  Three *
8.  No of windings per phase :  Two *
9.  Winding Connections :  Star – Star
10.  Type of transformer :  Earthed
11.  Rated Burden per phase :  As per requirement
12.  Class of Accuracy :  As per requirement
13.  Polarity :  Not applicable
14.  Rated voltage factor and time :  1.2 continuous *
15.  Limits of ratio and phase error :  Within limits specified by IS
16.  Temperature rise of top oil at 1.1 times rated primary voltage with rated secondary :  Within limits specified by IS
17.  H.V. Insulation characteristic of porcelain bushing
     a. Type :  Outdoor, Glazed Porcelain to IS 2099. *
     b. Make :  Suitable indigenous
     c. Electrical characteristics :  To IS 2099 / 3347 *
     d. Total creepage distance :  192 mm minimum. *
18.  One-minute power frequency withstand test on primary winding :  28 kV. *
19.  One-minute power frequency withstand test on secondary winding :  3 kV. *
20.  High voltage impulse withstand test on primary Windings :  75 kV. *
21.  One-minute power frequency withstand test on secondary winding :  Oil :
     a. Specification :  To IS 335 *
     b. Quantity for First Filling :  Approx. 30 Litres.
22.  Total weight of P.T. with oil :  Approx. 90 kgs.
23.  Reference specification :  IS 3156
24.  Outline dimensional drawing with mounting details :  As per drawing
24.  The potential transformers shall carry 50% above the rated burden continuously without injury but the accuracies will not be maintained at these higher burdens.

Note: Only items marked * are guaranteed. All others are indicative and subject to change.

]]>
260